ACT20M-RTI-AO-S
         

Icon
Icon
Icon
Icon
Icon
Icon
 

General ordering data

Version Temperature converter, With galvanic isolation, Input : Temperature, PT100, Output : I / U
Order No. 1375510000
Type ACT20M-RTI-AO-S
GTIN (EAN) 4050118259667
Qty. 1 pc(s).

Dimensions and weights

Depth 114.3 mm
Depth (inches) 4.5 inch
Height 112.5 mm
Height (inches) 4.429 inch
Width 6.1 mm
Width (inches) 0.24 inch
Net weight 89 g

Temperatures

Storage temperature -40 °C...85 °C
Operating temperature -25 °C...70 °C
Humidity at operating temperature 0...95 % (no condensation)
Humidity 40 °C / 95 % rel. humidity, no condensation

Probability of failure

MTBF 152 a

Environmental Product Compliance

REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924

Input

Influence of the sensor cable resistance <0.002 Ω/Ω (@ 3/4-wire)
Line resistance in measuring circuit ≤ 50 Ω
Number of inputs 1
Sensor PT100 (2-/3-/4- wire)
Temperature input range Configurable, PT100: -200…+850 °C, min. measurement range 10°C (RTD)

Output

Load impedance current ≤ 600 Ω
Number of outputs 1
Output current configurable, 0...20 mA, 4...20 mA
Output signal limit <4 mA (average), <60 mA (pulse current), low duty cycle
Output voltage, note configurable, 0(2)...10 V, 0(1)...5 V
Type active, connected control must be passive
Wire break detection Yes, Configurable, 3.5 mA / 23 mA / none
load impedance voltage ≥ 10 kΩ

General data

Accuracy absolute accuracy: <±0.05 % of the measurement range, Basic accuracy: <±0.1°C
Configuration DIP switch
Delivery state Output: 4...20 mA // Sensor error detection: enabled // Output error level: downscale // Noise suppression: 50 Hz // Step response time: < 30 ms // Start temperature: -200 °C // End temperature: 0 °C
Delivery state
Setting parameters Output
Configuration 4...20 mA
Setting parameters Sensor error detection
Configuration enabled
Setting parameters Output error level
Configuration downscale
Setting parameters Noise suppression
Configuration 50 Hz
Setting parameters Step response time
Configuration < 30 ms
Setting parameters Start temperature
Configuration -200 °C
Setting parameters End temperature
Configuration 0 °C
Galvanic isolation 3-way isolator
Included in delivery Instruction sheet
Power consumption, max. 0.7 W
Power consumption, typ. 0.49 W
Rail TS 35
Step response time Configurable, ≤ 30 ms, <300 ms
Temperature coefficient ≤0.01 % of the measurement range⁄°C or 0.02 °C ⁄ °C
Voltage supply 24 V DC ±30 % at terminal or via CH20M rail bus

Insulation coordination

EMC standards IEC 61326-1, NE 21
Galvanic isolation 3-way isolator
Insulation voltage 2.5 kVeff /1 min.
Pollution severity 2
Rated voltage 300 Veff
Surge voltage category II

Data for Ex applications (ATEX)

Installation location Device installed in safe area, zone 2
Marking II 3 G Ex nA IIC T4 Gc

Connection data

Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 30
Wire connection cross section AWG, max. AWG 14

EMC conformity and approvals

EMC standards IEC 61326-1, NE 21
Standards IEC 61010-1

Important note

Product information The ACT20M-RTI-AO-S configurable temperature transducer isolates and converts analogue signals. An analogue RTD input signal (Type Pt100) is linearly converted into an analogue output signal and galvanically isolated. The power supply is galvanically isolated from the input and output (3-way isolation) and this is done with direct wiring or over the Weidmüller rail bus.

Downloads

Approval/Certificate/Document of Conformity
Engineering Data
Engineering Data Zuken E3.S
Eplan Data Portal Eplan data
CADENAS eCATALOG CAX data
WSCAD Universe WSCAD data
Software
User Documentation
Catalogues Catalogues in PDF-format
Brochures

Classifications

ETIM 6.0 EC002919
ETIM 7.0 EC002919
ETIM 8.0 EC002919
ETIM 9.0 EC002919
ECLASS 9.0 27-21-01-29
ECLASS 9.1 27-21-01-29
ECLASS 10.0 27-21-01-29
ECLASS 11.0 27-21-01-29
ECLASS 12.0 27-21-01-29
ECLASS 13.0 27-21-01-29

Approvals

Approvals CULUS DETNORVER FMEX IECEXKEM KEMAATEX UKEX
ROHS Conform
UL File Number Search UL Website
Certificate no. (cULus) E337701

Related products

Type of connection: Screw connection
Order No.: 1375520000
Type: ACT20M-RTI-AO-E-S
Version:
Temperature converter, Without galvanic isolation, Input : Temperature, PT100, Output : I / U
 
Type of connection: Screw connection
Order No.: 1375480000
Type: ACT20M-TCI-AO-S
Version:
Temperature converter, Thermocouple, With galvanic isolation, Input : Temperature, thermocouple, Output : I / U
 
Type of connection: Screw connection
Order No.: 1375500000
Type: ACT20M-TCI-AO-E-S
Version:
Temperature converter, Thermocouple, Without galvanic isolation, Input : Temperature, thermocouple, Output : I / U
 
Type of connection: Screw connection
Order No.: 1435590000
Type: ACT20M-RTCI-CO-OLP-S
Version:
Passive isolator, With galvanic isolation, Input : Temperature, PT100, thermocouple, Output : 4-20 mA
 
Type of connection: Screw connection
Order No.: 1435610000
Type: ACT20M-RTI-CO-EOLP-S
Version:
Passive isolator, Without galvanic isolation, Input : Temperature, PT100, Output : 4-20 mA
 
Contact
Weidmüller Interface GmbH & Co. KG
 
+49 5231 14-0
+49 5231 14-292083
More information
Decentralised automation solutions
Energy Management Solutions
Industrial Analytics
Industrial IoT Solutions
More information
Mobility Concepts
Photovoltaics
Wind Solutions
Workplace Solutions
More information
Single Pair Ethernet
Weidmüller Configurator
Support & Service
Contact
Disposal Instructions
Engineering data
Repairs and replacement parts