General ordering data

Version Input : universal U, I, R,ϑ, Output : I/U universal, 2 x relays
Order No. 8939680000
Type WAZ6 TTA
GTIN (EAN) 4032248721085
Qty. 1 pc(s).
Delivery status This article will no longer be available in the future.
Available until 2023-12-30
Alternative product 1481960000

Dimensions and weights

Depth 112.4 mm
Depth (inches) 4.425 inch
Width 45 mm
Width (inches) 1.772 inch
Length 100 mm
Length (inches) 3.937 inch
Net weight 274 g

Temperatures

Storage temperature -40 °C...85 °C
Operating temperature 0 °C...70 °C
Humidity at operating temperature 0...95 % (no condensation)
Humidity 5...95 %, no condensation

Probability of failure

SIL in compliance with IEC 61508 None
MTTF 138 a

Environmental Product Compliance

REACH SVHC Lead 7439-92-1, 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol 119-47-1
SCIP f8333314-0c66-4444-aa47-78252861a7fb

Input

Input current -20...+50 mA (min. interval 0.4 mA)
Input frequency adjustable, 2 Hz…100 kHz
Input voltage -200...500 mV (min. 4 mV span), -20...50 V DC (min. 0.5 V span)
Number of inputs 1
Potentiometer 10…50 Ω, 50…100 Ω, 100…200 Ω, 200…400 Ω, 400…800 Ω, 800 Ω…2 kΩ, 2…6.5 kΩ, 6.5…100 Ω
Resistance 10 Ω…5 kΩ
Sensor Thermocouples: B, E, J, K, L, N, R, S, T (IEC 60584), PT100, PT1000, (EN 60571) Ni100, Ni1000, (JIS1604), Cu10, Cu25, Cu50, Cu100 (DIN 43760) 2-/3-/4-wire
Sensor supply 24 V DC / 22 mA
Temperature input range Configurable, B: +100…+1820 °C, E: -270…+1000 °C, J: -270…+1200 °C, K: -150…+1372 °C, L: +100…+900 °C, N: -180…+1300 °C, R: -50…+1768 °C, S: -50…+1768 °C, T: -270…+400 °C, U: -200…+600 °C, User defined

Output

Load impedance current ≤ 600 Ω, @ max 23mA

Output (digital)

Alarm function Top and bottom limit values, window range, Over-temperature, Alarm mode: delay, switch on or switch on/off, Holding function can be activated, Delayed 0...4200 s
Continuous current 2 A
Max. switching voltage, AC 0 V
Number of digital outputs
Rated switching current 0.1 A
Type 2 x 1 CO contact (hard gold-plated), Process alarms (4x) with hysteresis, with alarm delay (configurable) 0…180 s

Output (analogue)

Load resistance current <700 Ω
Load resistance voltage > 10 kΩ @ 0...10 V / > 20 kΩ @ -10...+10 V
Number of analogue outputs
Output current adjustable between 0 and 20 mA (min. span of 5 mA)
Output voltage adjustable between -10...+10 V (min. span 2.5 V)
Signal output direct or inverted
Transmit function Linear, x1/2, x3/2, x5/2 or user-defined curve (101 points)

General data

Accuracy <0.1 % span (DC, RTD); 0.2 % span (or 1 °C) + CJ failure
Configuration Using free Windows software, TTA Set Software, Requires configuration adapter 8978580000 CBX200 USB
Long-term drift 0
Power consumption <3.5 W
Step response time 50 ms...1 sec (RTD, mV inputs), 110 ms...1 sec (V, mA inputs)
Temperature coefficient <0.1 % / K (DC, RTD); <0.1 % FSR / K + CJ error 0.07 °C/K (thermocouples)
Voltage supply 18...264 V AC/DC

Insulation coordination

EMC standards EN 55011, EN 61000-6
Impulse withstand voltage 6 kV
Insulation voltage 2.5 kV
Pollution severity 2
Rated voltage 300 V
Surge voltage category III

Connection data

Type of connection Tension-clamp connection
Stripping length, rated connection 7 mm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²

Important note

Product information

WAS/WAZ6 TTA is a universal signal converter and trip amplifier that can be configured on the PC. Combines the functions of isolation, transmission, linearisation and trip amplification in a single module.

These exceptional characteristics and outstanding configurability combine to make the TTA truly unique. 
The TTA functions with stability and precision under a wide range of voltages and ambient temperatures. It is compatible with all standard sensor types.
 

  • Universal input signals: temperature signals such as resistance thermometer, thermocouple, potentiometer, frequency transmitter, DC voltage signals and current signals
  • Loop-powered or passive input
  • Wide-range power supply: 18 – 264 V AC/DC
  • User-defined linearization
  • Inputs and outputs can be configured on PC
  • Combined analogue and relay output
  • Ambient temperature range: -40 °C …70 °C



The CBX200 USB interface is used to connect to the PC.
The WAS/WAZ6 TTA is also offered as an option with ATEX Zone 2 and UL C1D2 approvals.


Downloads

Classifications

ETIM 6.0 EC002653
ETIM 7.0 EC002653
ETIM 8.0 EC002653
ETIM 9.0 EC002653
ECLASS 9.0 27-21-01-20
ECLASS 9.1 27-21-01-20
ECLASS 10.0 27-21-01-20
ECLASS 11.0 27-21-01-20
ECLASS 12.0 27-21-01-20
ECLASS 13.0 27-21-01-20

Tender specification sheets

Long specification

Universal measurement isolating converters and trip amplifiers; can be configured with a PC
Universal measurement isolating converters and trip amplifiers in 45 mm width with external supply
for voltage and sensors, for transmitting and isolating analogue DC current
-20 to 50 mA, voltages -200 to 500 mV/ -20 to 50 V, 2-/3-/-4-wire RTD, resistors,
thermocouples according to IEC 584 and frequencies up to 100 kHz( 2- / 3-wire sensors).
Two switching outputs (CO contact) for alarms
and analogue DC voltages (-10 to +10 V) and current outputs (0 to 20 mA) are available on the output side.
The component can be configured with a PC using the proprietary TTA-Set software.

Add-on housing for TS35 DIN rail installation
Dimensions: L/W/H 100/ 45/ 112.4 mm
tension-clamp connection/nominal cross-section1.5 mm2
Protection degree: IP20 input-20 to 50 mA -200 to 500 mV / -10 to +10 V PT100, PT1000, Ni100, Ni1000, Cu10/25/50/100 2-/3-/4-wire
resistance 10 Ohm to 5 kOhm/ Potentiometer100 Ohm to 100 kOhm
thermocouple types B, E, J, K, N, R, S, T
frequencies 2 Hz to 100 kHz (2-/3-wire sensors)

sensor supply 24 VDC / 22 mA outputanalogue0 to 20 mA / adjustable
-10 to +10 V/ adjustable
relay output/ Alarm 2 CO contacts, hard gold-plated
250 VAC @ 3 A / 30 VDC @ 2A

load resistance <700 Ohm/ current/ >10 kOhm/ voltageTransmission errorStep response time< 0,1 % v. E. (DC, RTD)
10...90 % < 0,2 % + CJ Fehler (TC)
Auxiliary power 18...264 V AC/DCPower loss approx. 3.5 WAmbient
temperature range -25 °C...+70 °C
< 50 ms...1 s einstellbar





< 50 ms...1 s einstellbar




< 50 ms...1 s einstellbar





Isolation EN 50178 secure 3-way isolation up to 6 kV of all circuits against each other
Test voltage 2.5 kV input against output against auxiliary power
Rated
voltage 300 V AC/DC at overvoltage category III and pollution degree 2
Approvals cULus, GL




Type WAZ6 TTA

Short specification Universal measurement isolating converters and trip amplifiers; can be configured with PC
Universal measurement isolating converters and trip amplifiers in 45 mm width with external supply
for voltage and sensors, for transmitting and isolating analogue DC current
 -20 to 50 mA, voltages -200 to 500 mV/ -20 to 50 V, 2-/3-/-4-wire RTD, resistors, 
thermocouples according to IEC 584 and frequencies up to 100 kHz( 2- / 3-wire sensors).
Two switching outputs (CO contacts) are available on the output side for alarms.
Analogue DC voltage (-10...+10 V) and current outputs (0...20 mA) are available on the output side.
The component can be configured with a PC using the proprietary TTA-Set software.

Approvals

Approvals CE CULUS
ROHS Conform
UL File Number Search UL Website
Certificate no. (cULus) E141197

Related products

Type of connection: Screw connection
Order No.: 8939670000
Type: WAS6 TTA
Version:
Input : universal U, I, R,ϑ, Output : I/U universal, 2 x relays
Delivery status:
This article will no longer be available in the future.
 
Type of connection: Screw connection
Order No.: 8964310000
Type: WAS6 TTA EX
Version:
Input : EX, universal U, I, R,ϑ, Output : I/U universal, 2 x relays
Delivery status:
This article will no longer be available in the future.
 
Type of connection: Tension-clamp connection
Order No.: 8964320000
Type: WAZ6 TTA EX
Version:
Input : EX, universal U, I, R,ϑ, Output : I/U universal, 2 x relays
Delivery status:
This article will no longer be available in the future.
 
Contact
Weidmüller Interface GmbH & Co. KG
 
+49 5231 14-0
+49 5231 14-292083
More information
Decentralised automation solutions
Energy Management Solutions
Industrial Analytics
Industrial IoT Solutions
More information
Mobility Concepts
Photovoltaics
Wind Solutions
Workplace Solutions
More information
Single Pair Ethernet
Weidmüller Configurator
Support & Service
Contact
Disposal Instructions
Engineering data
Repairs and replacement parts