A2C 35 PE
         

Icon
Icon
 

General ordering data

Version PE terminal, PUSH IN, 35 mm², 1000 V, Green/yellow
Order No. 2551520000
Type A2C 35 PE
GTIN (EAN) 4050118680201
Qty. 10 pc(s).

Dimensions and weights

Depth 71.5 mm
Depth (inches) 2.815 inch
Height 101 mm
Height (inches) 3.976 inch
Width 16 mm
Width (inches) 0.63 inch
Net weight 109.905 g

Temperatures

Storage temperature -25 °C...55 °C
Continuous operating temp., min. -60 °C
Continuous operating temp., max. 130 °C

Material data

Material Wemid
Colour Green/yellow
Colour of operational elements orange
UL 94 flammability rating V-0

Rating data IECEx/ATEX

Certificate No. (ATEX) TUEV16ATEX7909U
Certificate No. (IECEX) IECEXTUR16.0036U
Wire cross section max. (ATEX) 35 mm²
Wire cross section max. (IECEX) 35 mm²

System specifications

End cover plate required No
Number of levels
Number of clamping points per level
Rail TS 35
N-function No
PE function Yes
PEN function Yes

Additional technical data

Snap-on Yes
Type of fixing Snap-on
Type of mounting TS 35, Snap-on

CSA rating data

Certificate No. (CSA) 200039-70089609
Wire cross section max. (CSA) 2 AWG
Wire cross section min. (CSA) 12 AWG

Conductors for clamping (rated connection)

Blade size 1.0 x 5.5 mm
Clamping range, max. 35 mm²
Clamping range, min. 2.5 mm²
Connection cross-section, stranded, max. 35 mm²
Connection cross-section, stranded, min. 10 mm²
Connection direction on side
Number of connections
Stripping length 25 mm
Twin wire-end ferrules, max. 10 mm²
Twin wire-end ferrules, min. 2.5 mm²
Type of connection PUSH IN
Wire connection cross section AWG, max. AWG 2
Wire connection cross section AWG, min. AWG 12
Wire connection cross section, finely stranded, max. 35 mm²
Wire connection cross section, finely stranded, min. 10 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max. 35 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min. 2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 35 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 2.5 mm²
Wire connection cross-section, solid core, max. 16 mm²
Wire connection cross-section, solid core, min. 2.5 mm²

General

Operating temperature range, max. 130 °C
Operating temperature range, min. -50 °C
Rail TS 35
Standards IEC 60947-7-2
Wire connection cross section AWG, max. AWG 2
Wire connection cross section AWG, min. AWG 12

Rating data

Rated cross-section 35 mm²
Rated voltage 1,000 V
Rated voltage to adjoining terminal 1,000 V
Rated DC voltage 1,500 V
Standards IEC 60947-7-2
Volume resistance according to IEC 60947-7-x 0.26 mΩ
Power loss in accordance with IEC 60947-7-x 4 W
Pollution severity 3
Surge voltage category III

UL rating data

Certificate No. (cURus) E60693
Conductor size Factory wiring max. (cURus) 2 AWG
Conductor size Factory wiring min. (cURus) 12 AWG
Conductor size Field wiring max. (cURus) 2 AWG
Conductor size Field wiring min. (cURus) 12 AWG
Voltage size B (cURus) 1000 V
Voltage size C (cURus) 1000 V
Voltage size D (cURus) 600 V

Downloads

Classifications

ETIM 6.0 EC000901
ETIM 7.0 EC000901
ETIM 8.0 EC000901
ETIM 9.0 EC000901
ECLASS 9.0 27-14-11-41
ECLASS 9.1 27-14-11-41
ECLASS 10.0 27-14-11-41
ECLASS 11.0 27-14-11-41
ECLASS 12.0 27-14-11-41
ECLASS 13.0 27-25-01-03

Approvals

Approvals CCCEX CE CSA CURUS IECEXTUR KEMAKEUR TUEVNATEX UKEX UKCA
UL File Number Search UL Website
Certificate No. (cURus) E60693

Related products

There are no products in this group.
Contact
Weidmüller Interface GmbH & Co. KG
 
+49 5231 14-0
+49 5231 14-292083
More information
Decentralised automation solutions
Energy Management Solutions
Industrial Analytics
Industrial IoT Solutions
More information
Mobility Concepts
Photovoltaics
Wind Solutions
Workplace Solutions
More information
Single Pair Ethernet
Weidmüller Configurator
Support & Service
Contact
Disposal Instructions
Engineering data
Repairs and replacement parts