Power Solid-State Relais, Solid state contactor, Rated control voltage: 4…32 V DC , Rated switching voltage: 42…600 V AC +10% -15%, Continuous current: 30 A
Order No.
2986920000
Type
PSSRN S 24VDC 1M K 600VAC 30A T
GTIN (EAN)
4099986853041
Qty.
1 pc(s).
Dimensions and weights
Depth
167.5 mm
Depth (inches)
6.594 inch
Height
110 mm
Height (inches)
4.331 inch
Width
22.5 mm
Width (inches)
0.886 inch
Net weight
370 g
Temperatures
Storage temperature
-40 °C...100 °C
Operating temperature
-25 °C...70 °C
Humidity
95% relative humidity, non-condensing @ 40°C
Probability of failure
MTTF
10 a
Environmental Product Compliance
RoHS Compliance Status
Compliant with exemption
RoHS Exemption (if applicable/known)
7cI
REACH SVHC
No SVHC above 0.1 wt%
Control side
Rated control voltage
4…32 V DC
Nominal control current
7.8 mA…10.4 mA
Status indicator
Green LED, Yellow LED, Red LED
Load side
Rated switching voltage
42…600 V AC +10% -15%
Continuous current
30 A (AC 51) @ 40 °C
Max. switching current
30 A
Load category
AC 51
Pulse load, max. current
1150 A (10 ms, non-recurrent)
Load limit integral (I²t) <10 ms
6,600 A²s
Switch-on delay
≤ 10 ms
Switch-off delay
≤ 10 ms
Voltage drop at max. load
≤20 V
Leakage current
<3 mA
Min. switching current
1.2 A
Short-circuit-proof
No
Protective circuit, load side
Integrated varistor
Contact type
1 NO contacts (Thyristor (zero-cross switch))
Output voltage frequency range
45…65 Hz
Alarm output
Connection designation (Alarm output)
11+, 12-
Solid-state type (Alarm output)
Bipolar transistor
Status indicator (Alarm output)
Red LED: device detects a fault
Voltage drop at max. load (Alarm output)
3 V
output current, max. (Alarm output)
50 mA
TEACH input
Connection designation (TEACH input)
IN1
Input supply
Connection designation (Input supply)
A1+, A2-
Current consumption (Input supply)
50 mA
Protective circuit (Input supply)
Reverse polarity protection
General data
Version
Single-phase with mounted heat sink (zero-voltage switch output)
Rail
TS 35
Colour
black
Insulation coordination
Pollution severity
2
Surge voltage category
III
Dielectric strength for control side - load side
2.5 kVeff
Dialectric strength of load side - housing
4 kVeff
Impulse withstand voltage
6 kV (1.2/50 µs)
Protection degree
IP20
Further details of approvals / standards
Certificate no. (cULus)
E537615
Connection data (control side)
Stripping length, control side
13 mm
Stripping length, two clampable wire, control side
6 mm
Wire connection cross-section, solid, control side, max.
2.5 mm²
Wire connection cross-section, solid, control side, max. (AWG)
AWG 18
Wire connection cross-section, solid, control side, min. (AWG)
AWG 12
Wire connection cross-section, twin wire-end ferrules, control side, max.
2.5 mm²
Wire connection cross-section, twin wire-end ferrules, control side, min.
1 mm²
Wire connection method (control side)
Box clamp connection
Min. rated connection clamping range (control side)
1 mm²
Max. rated connection clamping range (control side)
Power Solid-State Relais, Solid state contactor, Rated control voltage: 4…32 V DC , Rated switching voltage: 42…600 V AC +10% -15%, Continuous current: 30 A
This function is provided via the external service provider https://supplyframe.com. By clicking on "Continue" you will be redirected to this page. This leads to a data transfer of personal data to non-European countries. Please check the data protection policy of the external website, for which Weidmüller assumes no responsibility and liability.