General ordering data

Version Measuring bridge converter, Input : Resistance measuring bridge, Output : 0(4)-20 mA, 0-10 V
Order No. 2456820000
Type ACT20P-BRIDGE-P
GTIN (EAN) 4050118471762
Qty. 1 pc(s).

Dimensions and weights

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 127.1 mm
Height (inches) 5.004 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 205 g

Temperatures

Storage temperature -40 °C...85 °C
Operating temperature -20 °C...60 °C
Humidity at operating temperature 0...95 % (no condensation)
Humidity 10…90 %, no condensation

Probability of failure

SIL in compliance with IEC 61508 None

Environmental Product Compliance

REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924

Input

Bridge sensitivity 1.0 mV / V to 5.0 mV / V
Bridge supply voltage 5 V or 10 V
Input signal ±10 mV / ±20 mV / ±30 mV / ±50 mV
Number of inputs 1
Sensor Strain gauge resistance, Resistance measurement, Total resistance of all parallel resistance measuring bridges: min. 87 Ω
Sensor supply 120 mA @ 10 V (= 4 x 350 Ω bridge resistors)

Output

Load impedance current ≤ 600 Ω
Output current 0…22 mA (adjustable)
Output voltage, note 0…11 V (adjustable)
Type active, connected control must be passive
load impedance voltage 600 Ω

General data

Accuracy <0.05 % of measuring range
Configuration DIP switch and button
Linearity Typically ± 0.05 % of signal range
Long-term drift 0.1 % / 10.000 h
Power consumption 3 W @ 24 V DC
Protection degree IP20
Rail TS 35
Step response time <400 ms (10…90 %)
Temperature coefficient typ. 0.005 % / °C
Voltage supply 10…60 V DC

Insulation coordination

EMC standards EN 61326
Insulation voltage 5.7 kV (input / output, input / supply)
Pollution severity 2
Rated voltage 300 V
Surge voltage category III

Connection data

Type of connection PUSH IN
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.2 mm²
Wire cross-section, solid, max. 2.5 mm²
Wire connection cross section, finely stranded, min. 0.2 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²

Important note

Product information The ACT20P-BRIDGE-P bridge measuring transducer converts measuring bridge voltages into standard signals. Buttons are used for adjustment to the measuring bridge connected. The bridge measuring transducer can supply up to 4 parallel-connected measuring bridges each with 350 Ω. The device supports simple compensation of the tare weight with a separate input for an external button or an external PLC signal. The power supply is galvanically isolated from input and output (3-way isolation).T

Features
  • 4-wire and 6-wire measurement
  • Supply of up to 4 parallel-connected measuring bridges each with 350 Ω
  • Input and output ranges can be adjusted via DIP switches
  • Tare compensation via external button or PLC signal
  • Front LED indicates operation status
  • 3-way galvanic isolation between input, output and power supply

Downloads

Approval/Certificate/Document of Conformity
Engineering Data
Eplan Data Portal Eplan data
CADENAS eCATALOG CAX data
Software
User Documentation
Catalogues Catalogues in PDF-format

Classifications

ETIM 6.0 EC002653
ETIM 7.0 EC002653
ETIM 8.0 EC002653
ETIM 9.0 EC002653
ECLASS 9.0 27-21-01-20
ECLASS 9.1 27-21-01-20
ECLASS 10.0 27-21-01-20
ECLASS 11.0 27-21-01-20
ECLASS 12.0 27-21-01-20
ECLASS 13.0 27-21-01-20

Approvals

Approvals CE
Approvals CULUS;
ROHS Conform

Related products

Order No.: 1067250000
Type of connection: Screw connection
Type: ACT20P BRIDGE
Version:
Measuring bridge converter, Input : Resistance measuring bridge, Output : 0(4)-20 mA, 0-10 V
 
Contact
Weidmüller Interface GmbH & Co. KG
 
+49 5231 14-0
+49 5231 14-292083
More information
Decentralised automation solutions
Energy Management Solutions
Industrial Analytics
Industrial IoT Solutions
More information
Mobility Concepts
Photovoltaics
Wind Solutions
Workplace Solutions
More information
Single Pair Ethernet
Weidmüller Configurator
Support & Service
Contact
Disposal Instructions
Engineering data
Repairs and replacement parts