ACT20X-HUI-SAO-LP-S
Do not use product for new developments
General ordering data
Version
ACT20X, EX signal isolating converter, 1-channel version, Output-loop powered
Order No.
1318220000
Type
ACT20X-HUI-SAO-LP-S
GTIN (EAN)
4050118323955
Qty.
1 pc(s).
Delivery status
This article will no longer be available in the future.
Available until
2021-12-15
Dimensions and weights
Depth
113.6 mm
Depth (inches)
4.472 inch
Height
117.2 mm
Height (inches)
4.614 inch
Width
12.5 mm
Width (inches)
0.492 inch
Net weight
171 g
Temperatures
Storage temperature
-20 °C...70 °C
Operating temperature
0 °C...60 °C
Humidity at operating temperature
0...95 % (no condensation)
Humidity
10…90 %, no condensation
Probability of failure
SIL in compliance with IEC 61508
2
Environmental Product Compliance
REACH SVHC
Lead 7439-92-1
SCIP
2f6dd957-421a-46db-a0c2-cf1609156924
RoHS Compliance Status
Compliant with exemption
RoHS Exemption (if applicable/known)
7a, 7cI
Assembling
Mounting position
horizontal or vertical
Rail
TS 35
Type of mounting
DIN rail
Input EX
Input current
configurable, ± 25 mA, 0...20 mA, 4…20mA
Input resistance
0…12 kΩ
Input resistance, current
70 Ω
Input resistance, voltage
> 10 MΩ @ 600 mV, 2 MΩ @ 28 V
Input voltage
configurable, ± 12 V DC (min. measurement range 1 V), ± 28 V DC (min. measurement range 2 V), ± 600 mV DC (min. measurement range 50 mV), ± 150 mV DC (min. measurement range 15 mV)
Line resistance in measuring circuit
≤ 50 Ω
Potentiometer
1.2…500 kΩ
Sensor
2-/3-/4-wire, RTD: PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120, Ni1000, Thermocouples: B, E, J, K, N, R, S, T ; in compliance with IEC 60584-1 and L, U in compliance with DIN43710, Potentiometer, Resistance: 0 - 12 kΩ
Sensor supply
28…16.5 V DC / 0…20 mA
Temperature input range
Adjustable from -200...+800°C
Type
intrinsically safe circuit
Output
Cut-off frequency (-3 dB)
100 Hz
Load impedance current
≤ 700 Ω
Output current
4…20 mA (max. 23 mA)
Output signal limit
3.8…20.5 mA / 0…20.5 mA (dependent on range)
Type
Output-loop powered
General specifications
Accuracy
<0.1 % of end value
Configuration
With FDT/DTM software, Requires configuration adapter 8978580000 CBX200 USB
Humidity
10…90 %, no condensation
Power consumption
≤ 3.5 W
Protection degree
IP20
Step response time
250 ms (10…90%)
Temperature coefficient
<0.02 °C of measuring range / °C
Type of connection
Screw connection
Voltage supply
via output current loop, 11…28 V DC (loop powered)
Insulation coordination
Impulse withstand voltage
4 kV (1.2/50 µs)
Insulation voltage
3.51 kV between input and output
Pollution severity
2
Rated voltage
300 Veff
Standards
DIN EN 61326-1, IEC 61010-1, IEC 61010-2-030, IEC 60079-0, IEC 60079-11, IEC 60079-15, IEC 60079-26
Surge voltage category
III
Data for Ex applications (ATEX)
Current I0
88.2 mA
Installation location
Device installed in safe area, zone 2
Marking
II 3 G Ex nA IIC T4 Gc, I (M1) [Ex ia Ma] I, II (1) D [Ex ia Da] IIIC
Ex universal measurement isolating transformer for RTD-/ TC temperature and DC-current-/ voltage signals, output-loop powered 1-channel 4...20 mA output-loop powered measurement isolating transformer in 12.5 mm width for recording, isolating and transmitting RTD- / TC sensors, resistors, potentiometers and DC current signals and voltages from Ex zones 0,1,2 to the safe zone. The component can be configured using standard FDT/DTM software. Add-on housing for TS35 rail mounting Dimensions: L/W/H 119.2/ 12.5/ 113.6 Screw connection/ Nominal cross-section 2.5 mm2 Protection degree: IP 20
Input RTD: PT200, PT1000, Ni120, Cu100 Resistance 0...15 kOhm / Potentiometer 1.2...500 kOhm TC- Type: B, E, J, K, L, N, R, S, T,U +/- 25 mA configurable +/- 28 V configurable Output 4...20 mA current loop Load < 700 Ohm Accuracy < 0,1 % v.E Auxiliary power 11...28 VDC / current loop Power loss approx. 1.5 W Ambient temperature range 0 °C...+60 °C
Secure isolation EN 50178, 2-way isolation up to 4kV Working voltage 300 V AC/DC at overvoltage category II and pollution degree 2 Approvals cULus, ATEX IECEX, Class1, Div1
IECEx marking (Exia)I IIC / I T4 Ex characteristic data U0 = 5.88 V DC I0 = 82.3 mA DC P0 = 121 mW TypeACT20X-HUI-SAO-LP-S
Short specification
Ex universal measurement isolating transformer for RTD-/ TC temperature and DC-current-/ voltage signals, output-loop powered 1-channel 4...20 mA- loop-powered measurement isolating transformer in 12.5 mm width for recording, isolating and transmitting RTD- / TC sensors, resistors, potentiometers and DC current signals and voltages from Ex zones 0,1,2 to the safe zone. The component can be configured using standard FDT/DTM software.
Approvals
Approvals
Approvals
CULUS; EAC; IECEXKEM; ATEX
ROHS
Conform
Related products:
Order No.:
8965490000
Type of connection:
Screw connection
Type:
ACT20X-HUI-SAO-S
Version:
EX signal isolating converter, Ex-output: U, I, R,ϑ, Safe-output: 4-20mA/ relay, 1-channel
configurable, ± 12 V DC (min. measurement range 1 V), ± 28 V DC (min. measurement range 2 V), ± 600 mV DC (min. measurement range 50 mV), ± 150 mV DC (min. measurement range 15 mV)
Line resistance in measuring circuit
≤ 50 Ω
Potentiometer
1.2…500 kΩ
Sensor
2-/3-/4-wire, RTD: PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120, Ni1000, Thermocouples: B, E, J, K, N, R, S, T ; in compliance with IEC 60584-1 and L, U in compliance with DIN43710, Potentiometer, Resistance: 0 - 12 kΩ
Ex universal measurement isolating transformer for RTD-/ TC temperature and DC-current-/ voltage signals, output-loop powered 1-channel 4...20 mA output-loop powered measurement isolating transformer in 12.5 mm width for recording, isolating and transmitting RTD- / TC sensors, resistors, potentiometers and DC current signals and voltages from Ex zones 0,1,2 to the safe zone. The component can be configured using standard FDT/DTM software. Add-on housing for TS35 rail mounting Dimensions: L/W/H 119.2/ 12.5/ 113.6 Screw connection/ Nominal cross-section 2.5 mm2 Protection degree: IP 20
Input RTD: PT200, PT1000, Ni120, Cu100 Resistance 0...15 kOhm / Potentiometer 1.2...500 kOhm TC- Type: B, E, J, K, L, N, R, S, T,U +/- 25 mA configurable +/- 28 V configurable Output 4...20 mA current loop Load < 700 Ohm Accuracy < 0,1 % v.E Auxiliary power 11...28 VDC / current loop Power loss approx. 1.5 W Ambient temperature range 0 °C...+60 °C
Secure isolation EN 50178, 2-way isolation up to 4kV Working voltage 300 V AC/DC at overvoltage category II and pollution degree 2 Approvals cULus, ATEX IECEX, Class1, Div1
IECEx marking (Exia)I IIC / I T4 Ex characteristic data U0 = 5.88 V DC I0 = 82.3 mA DC P0 = 121 mW TypeACT20X-HUI-SAO-LP-S
Short specification
Ex universal measurement isolating transformer for RTD-/ TC temperature and DC-current-/ voltage signals, output-loop powered 1-channel 4...20 mA- loop-powered measurement isolating transformer in 12.5 mm width for recording, isolating and transmitting RTD- / TC sensors, resistors, potentiometers and DC current signals and voltages from Ex zones 0,1,2 to the safe zone. The component can be configured using standard FDT/DTM software.
This function is provided via the external service provider https://supplyframe.com. By clicking on "Continue" you will be redirected to this page. This leads to a data transfer of personal data to non-European countries. Please check the data protection policy of the external website, for which Weidmüller assumes no responsibility and liability.