General ordering data

Version Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) ≤ 1870 V
Order No. 1066490000
Type VSSC6TRCLFG24VAC/DC EX
GTIN (EAN) 4032248820122
Qty. 1 pc(s).

Dimensions and weights

Depth 81 mm
Depth (inches) 3.189 inch
Height 88.5 mm
Height (inches) 3.484 inch
Width 12.4 mm
Width (inches) 0.488 inch
Net weight 60.6 g

Temperatures

Storage temperature -40 °C...80 °C
Operating temperature -40 °C...70
Humidity 5...96 %

Probability of failure

SIL in compliance with IEC 61508 3
MTTF 3,936 a
SFF 93.28 %
λges 29 
PFH in 1*10-9 per hour 1.95 

Environmental Product Compliance

RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 71e97bb7-979f-4330-94c0-20c629bb05e3

Protection Ex - Data

ATEX - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
ATEX - gas labelling II 1 G Ex ia IIC T4… T6 Ga
IECEx - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
IECEx - gas labelling II 1 G Ex ia IIC T4… T6 Ga
Input power, max. PI 0.75 W
Input voltage, max. Ui 42 V
Internal capacity, max. CI 2 nF
Internal inductance, max. LI 0 µH
Temperature class T4/135°C (-40°C ... +120 °C) li 300 mA
Temperature class T5/100°C (-40 ° C ... +85 °C) li 300 mA
Temperature class T6/85 °C (-40 °C ... +70 °C) li 300 mA

CSA protection data

Gas group C IIB
Gas group D IIA
Gas groups A, B IIC
Input current, max. II 300 mA
Input voltage, max. Ui 42 V
Internal capacity, max. CI 1 nF
Internal inductance, max. LI 0 µH

General data

Number of poles 1
Protection degree IP20
Colour Light Blue

Insulation coordination acc. to EN 50178

Pollution severity 2
Surge voltage category III

Rated data IEC / EN

Dielectric strength at FG against PE ≥ 500 V
Discharge current Imax (8/20µs) wire-PE 5 kA
Discharge current Imax (8/20µs) wire-wire 5 kA
Discharge current In (8/20µs) wire-PE 2.5 kA
Discharge current In (8/20µs) wire-wire 2.5 kA
Discharge current, max. (8/20 µs) 10 kA
Input voltage, max. Ui 42 V
Insertion loss 250 MHz
Lightning test current Iimp (10/350 µs) 0.5 kA
Lightning test current, Iimp (10/350 µs) Wire-PE 0.5 kA
Max. continuous voltage, Uc (AC) 30 V
Max. continuous voltage, Uc (DC) 42 V
Number of poles 1
Overload - failure mode Modus 2
Protection level UP (typ.) ≤ 1870 V
Protection level on output side Wire-wire 1 kV/µs, typically 70 V
Protection level, UP wire - wire 90 V
Pulse-reset capacity ≤ 20 ms
Rated current IN 300 mA
Rated voltage (AC) 24 V
Rated voltage (DC) 34 V
Requirements category acc. to IEC 61643-21 C2, C3, D1
Signal transmission properties (-3 dB) 270 Mhz
Standards IEC61643-21:2009, DIN EN 60079-0.2009, DIN EN 60079-26:2007, DIN EN 61241-11:2006, HART-compatible
Surge current-carrying capacity C2 2.5 kA 8/20 µs 5 kV 1.2/50 µs
Surge current-carrying capacity C3 50 A 10/1000 μs
Surge current-carrying capacity D1 0.5 kA 10/350 μs
Voltage type DC
Volume resistance 1.8 Ω 10 %

Further details of approvals

GOST certificate GOST-Zertifikat

Connection data

Stripping length 10 mm
Type of connection Screw connection
Tightening torque, min. 0.5 Nm
Tightening torque, max. 0.8 Nm
Clamping range, min. 0.5 mm²
Clamping range, max. 4 mm²
Wire cross-section, solid, min. 0.5 mm²
Wire cross-section, solid, max. 6 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min. 0.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max. 4 mm²
Connection cross-section, stranded, min. 0.5 mm²
Connection cross-section, stranded, max. 4 mm²

Electrical data

Voltage type DC

Ratings IECEx/ATEX/cUL

ATEX - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
ATEX - gas labelling II 1 G Ex ia IIC T4… T6 Ga
ATEX certificate ATEX Certificate
IEC Ex certificate IECEX Zertifikat
IECEx - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
IECEx - gas labelling II 1 G Ex ia IIC T4… T6 Ga
cUL certificate cUL Certificate

Important note

Product information Mode 2: State where the voltage-limiting part of the SPD was short-circuited due to a very low impedance within the SPD. The line is inoperable, but the measuring equipment is still protected by means of a short-circuit.

Downloads

Classifications

ETIM 6.0 EC000943
ETIM 7.0 EC000943
ETIM 8.0 EC000943
ETIM 9.0 EC000943
ECLASS 9.0 27-13-08-07
ECLASS 9.1 27-13-08-07
ECLASS 10.0 27-13-08-07
ECLASS 11.0 27-13-08-07
ECLASS 12.0 27-17-90-90
ECLASS 13.0 27-17-90-90
ECLASS 14.0 27-17-90-90

Tender specification sheets

Long specification Surge protection in a one piece, 12.4 mm wide terminal rail module for a floating-ground, intrinsically safe signal circuit with 48 VUC in 2-wire technology. A current loop with max. 0.6 A can be protected here. Each signal path can be opened using an isolator. When the terminal is fitted, a sparkover gap is simultaneously created to the high-impedance earth between the terminal rail (earth) and the reference potential (ground) of the protective circuit. Optical identification of the terminal based on the type of protective circuit and the voltage level. The terminal can be labelled.
Short specification Surge protection in a one piece, 12.4 mm wide terminal rail module for an intrinsically safe, floating-ground driven signal circuit with 2-wire technology and a common wire. Each signal path can be opened using an isolator. Version: 48 VUC

Approvals

Approvals CE CSAEX DEKRAATEX FUSAFETY IECEXDEK
ROHS Conform

Related products

Type of connection: Screw connection
Order No.: 1064260000
Type: VSSC6 CL FG 12VDC 0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) 1600 V
 
Type of connection: Screw connection
Order No.: 1064270000
Type: VSSC6 CLFG24VAC/DC0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) 1632 V
 
Type of connection: Screw connection
Order No.: 1064280000
Type: VSSC6 CLFG48VAC/DC0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) ≤ 1510 V
 
Type of connection: Screw connection
Order No.: 1064290000
Type: VSSC6 CLFG60VAC/DC0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) ≤ 1510 V
 
Type of connection: Screw connection
Order No.: 1064300000
Type: VSSC6TRCLFG12VDC0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) ≤ 1.7 kV
 
Type of connection: Screw connection
Order No.: 1064310000
Type: VSSC6TRCLFG24VAC/DC0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) ≤ 1650 V
 
Type of connection: Screw connection
Order No.: 1064320000
Type: VSSC6TRCLFG48VAC/DC0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) ≤ 1550 V
 
Type of connection: Screw connection
Order No.: 1064330000
Type: VSSC6TRCLFG60VAC/DC0.5A
Version:
Surge protection for instrumentation and control, Surge protection for measurement and control, UP(L/N-PE) ≤ 1550 V
 
Contact
Weidmüller Interface GmbH & Co. KG
 
+49 5231 14-0
+49 5231 14-292083
More information
Decentralised automation solutions
Energy Management Solutions
Industrial Analytics
Industrial IoT Solutions
More information
Mobility Concepts
Photovoltaics
Wind Solutions
Workplace Solutions
More information
Single Pair Ethernet
Weidmüller Configurator
Support & Service
Contact
Disposal Instructions
Engineering data
Repairs and replacement parts