WAZ5 DC/ALARM
         

Icon
Icon
Icon
 

General ordering data

Version Limit value monitoring, Input : 0-20 mA, 0-10 V, Output : 2 x relays
Order No. 8543880000
Type WAZ5 DC/ALARM
GTIN (EAN) 4032248181247
Qty. 1 pc(s).
Delivery status This article will no longer be available in the future.
Available until 2023-12-30
Alternative product 2456840000

Dimensions and weights

Depth 112.4 mm
Depth (inches) 4.425 inch
Width 17.5 mm
Width (inches) 0.689 inch
Length 92.4 mm
Length (inches) 3.638 inch
Net weight 141 g

Temperatures

Storage temperature -20 °C...85 °C
Operating temperature 0 °C...55 °C
Humidity at operating temperature 0...95 % (no condensation)
Humidity 40 °C / 93 % rel. humidity, no condensation

Probability of failure

SIL in compliance with IEC 61508 None
MTTF 369 a

Environmental Product Compliance

REACH SVHC Lead 7439-92-1
SCIP c2a21576-d875-4548-ae68-5e7f85ddf0c7

Input

Input current 0(4)...20 mA
Input resistance, current ≤ 110 Ω
Input resistance, voltage ≥ 100 kΩ
Input voltage 0...10 V
Number of inputs 1

Output (digital)

Alarm function configurable, High or low alarm, Hysteresis 5% / 10%
Contact material AgNi 90/10
Continuous current 3 A
Hysteresis 1...10 % (independent for channel 1 and channel 2)
Max. switching frequency 20 Hz
Max. switching voltage, AC 250 V
Status indicator LED green ON: OK, LED red ON: alarm (per channel)
Switching thresholds 1...90 % (independently for channel 1 and channel 2)
Type 2 CO contacts, Open or closed-circuit principle

General data

Accuracy Repeat accuracy: max. ± 0.3% of measuring range end value (10 V/ 20 mA)
Configuration DIP switch, Potentiometer
Galvanic isolation 3-way isolator
Power consumption Typ.: 1 W both relays picked up
Rail TS 35
Temperature coefficient ≤ 500 ppm/K
Voltage supply 24 V DC ± 25 %

Insulation coordination

EMC standards EN 61000-4-2, -3, -4, -5, -6
Galvanic isolation 3-way isolator
Impulse withstand voltage 4 kV
Insulation voltage 2 kVeff / 5 s
Pollution severity 2
Rated voltage 300 V
Surge voltage category III

Connection data

Type of connection Tension-clamp connection
Clamping range, rated connection 1.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²

Important note

Product information This product will soon be replaced by a new product.
Please do not use with new systems. Please contact our technical support.

Downloads

Approval/Certificate/Document of Conformity
Engineering Data
CADENAS eCATALOG CAX data
Product Change Notification
User Documentation
Catalogues Catalogues in PDF-format
Brochures

Classifications

ETIM 6.0 EC002654
ETIM 7.0 EC002654
ETIM 8.0 EC002654
ETIM 9.0 EC002654
ECLASS 9.0 27-21-01-22
ECLASS 9.1 27-21-01-22
ECLASS 10.0 27-21-01-22
ECLASS 11.0 27-21-01-22
ECLASS 12.0 27-21-01-22
ECLASS 13.0 27-21-01-22

Tender specification sheets

Long specification

Limit-value monitoring component for DC- current-/ voltage standard signals with relay output
and 3-way electrical isolation.
Limit-value monitoring component in 22.5 mm width for recording 0(4)...20 mA / 0...10 V
standard signals. Two relay contacts (COs), each with a switching capacity of 750 VA, are available on the output side for monitoring an upper and lower limit.

The switching behaviour (high/low trip,  fail-safe) can be selected using DIP switches.
Switching thresholds and hystereses are adjustable using the front-side potentiometer. The component has
4 kV of 3-way isolation and is supplied externally with 24 VDC.

Add-on housing for TS35 rail mounting
Dimensions: L/W/H 92.4/ 22.5/ 112.4 mm
Tension-clamp connection / Nominal cross-section 1.5 mm2
Protection degree: IP 20  


Input                         0(4)...20 mA / 0...10 V
Output                                             2 x relay / CO
                                      Open-circuit/closed-circuit principle
Switching current 3 A
Switching voltage 6... 250 V AC / 6...60 V DC
Switching thresholds 1...90 % via potentiometer (independently for channels 1 and 2)
Hysteresis                     1% ... 10 % via potentiometer (independently for channels 1 and 2)
Temperature coefficient   < 500 ppm K
Step response time        < 60 ms (10...90 %)
Auxiliary power                                     24 VDC +/- 25 %
Ambient
temperature range 0 °C...+55 °C

Secure isolation                   EN 50178, 3-way Isolation up to 4 kV
Test voltage                               2 kVeff / 5s Input / Output/ Supply
Rated
voltage                                         
 300 V AC/DC at overvoltage category III and pollution degree 2
Approvals cULus




Type                                                             WAZ5 DC/Alarm

Short specification

Limit-value monitoring component for DC- current/voltage standard signals with relay output
and 3-way electrical isolation.
Limit-value monitoring component in 22.5 mm width for recording 0(4)...20 mA / 0...10 V
standard signals.  Two relay contacts (COs), each with a switching capacity
of 750 VA, are available on the output side for monitoring an upper and lower limit.
The switching behaviour (high/low trip,  fail-safe) can be selected using DIP switches.
Switching thresholds and hystereses are adjustable using the front-side potentiometer. The component has
4 kV of 3-way isolation and is supplied externally with 24 VDC.

Approvals

Approvals CE CULUS
ROHS Conform
UL File Number Search UL Website
Certificate no. (cULus) E141197

Related products

Type of connection: Screw connection
Order No.: 8543820000
Type: WAS5 DC/ALARM
Version:
Limit value monitoring, Input : 0-20 mA, 0-10 V, Output : 2 x relays
Delivery status:
This article will no longer be available in the future.
 
Type of connection: Screw connection
Order No.: 8705630000
Type: WAS2 VMR 3PH
Version:
WAVESERIES, Voltage monitoring, 1 x three-phase (R, S, T, N), 250 V, Screw connection
Delivery status:
This article will no longer be available in the future.
 
Contact
Weidmüller Interface GmbH & Co. KG
 
+49 5231 14-0
+49 5231 14-292083
More information
Decentralised automation solutions
Energy Management Solutions
Industrial Analytics
Industrial IoT Solutions
More information
Mobility Concepts
Photovoltaics
Wind Solutions
Workplace Solutions
More information
Single Pair Ethernet
Weidmüller Configurator
Support & Service
Contact
Disposal Instructions
Engineering data
Repairs and replacement parts