General ordering data

Version Surge voltage arrester, Low voltage, without telecomm. contact, TN-C-S, TN-S
Order No. 1438010000
Type VPU I 4 400V/25KA
GTIN (EAN) 4050118243703
Qty. 1 pc(s).

Dimensions and weights

Depth 69 mm
Depth (inches) 2.717 inch
Height 106 mm
Height (inches) 4.173 inch
Width 142.4 mm
Width (inches) 5.606 inch
Mounting dimension - height 75 mm
Net weight 1,530 g

Temperatures

Storage temperature -40 °C...80 °C
Operating temperature -40 °C...70
Humidity 5 - 95% rel. humidity

General data

Colour black, orange
Design Installation housing; 8 TE, Insta IP 20
Operating altitude ≤ 2000 m
Optical function display green = OK; red = arrester is defective - replace
Protection degree IP20
Rail TS 35
Segment Power distribution
UL 94 flammability rating V-0
Version without telecomm. contact

Insulation coordination acc. to EN 50178

Pollution severity 2
Surge voltage category IV

Rated data IEC / EN

Discharge current Imax (8/20µs) wire-PE 100 kA
Discharge current In (8/20µs) wire-PE 25 kA
Energy coordination (≤10 m) Type I, Type II, Type III
Follow-on current extinguishing capability Ifi Not available due for technical reasons
Frequency range, max. 60 Hz
Frequency range, min. 50 Hz
Fuse No Fuse neccessary ≤250 A gG, 250 A gL (if back up fuse > 250 A)
Leakage current at Un 100 µA
Lightning test current Iimp (10/350 µs) (L-PE) 25 kA
Low voltage network TN-C-S, TN-S
Mains voltage 230 V / 400 V, 400 V / 690 V
Max. continuous voltage, Uc (AC) 400 V
Number of poles 4
Protection level Up at IN (L/N-PE) ≤ 1.9 kV
Rated load current IL 100 A
Rated voltage (AC) 400 V
Requirements category acc. to IEC 61643-11 Type I, Type II
Requirements class, acc. to EN 61643-11 T1, T2
Response time ≤ 25 ns
Short-circuit current rating ISCCR 25 kA
Signalling contact No
Standards IEC61643-11, EN61643-11
Temporary surge voltage (over-voltage) - TOV 620 V
Voltage type AC

Connection data

Stripping length 15 mm
Type of connection Screw connection
Stripping length, rated connection 15 mm
Tightening torque, min. 2 Nm
Tightening torque, max. 3 Nm
Clamping range, rated connection 16 mm²
Clamping range, min. 4 mm²
Clamping range, max. 35 mm²
Wire cross-section, solid, min. 2.5 mm²
Wire cross-section, solid, max. 16 mm²
Wire connection cross section, finely stranded, min. 2.5 mm²
Wire connection cross section, finely stranded, max. 25 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min. 2.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max. 50 mm²
Connection cross-section, stranded, min. 2.5 mm²
Connection cross-section, stranded, max. 50 mm²

Downloads

Approval/Certificate/Document of Conformity
Engineering Data
Eplan Data Portal Eplan data
CADENAS eCATALOG CAX data
WSCAD Universe WSCAD data
User Documentation
Catalogues Catalogues in PDF-format
Brochures

Classifications

ETIM 6.0 EC000941
ETIM 7.0 EC000941
ETIM 8.0 EC000941
ETIM 9.0 EC000941
ECLASS 9.0 27-13-08-05
ECLASS 9.1 27-13-08-05
ECLASS 10.0 27-13-08-05
ECLASS 11.0 27-13-08-05
ECLASS 12.0 27-17-90-90
ECLASS 13.0 27-17-90-90

Tender specification sheets

Long specification Multi-pin lightning arrestor according to the requirements of Class I in accordance with IEC 61643-11, EN61643-11:2013. On interface transition from 0 to 1 (acc. to IEC 1312-1), the arrestor serves as lightning protection providing equipotential bonding and is used in applications in accordance with IEC 61643-12. The use of a no-blow-out spark gap, in combination with a high-power varistor, fulfils the inspection requirements for Class I surge protection systems according to the VDEW (Association of German Power Stations) directive. The arrester is installed in a commercially available installation/electrical distribution enclosure, in the vicinity of the power-supply unit for the equipment that needs protection. The VPU I 3+1 R 400 V/25 kA is used in the TN-C and TN-C mains network. With thermal separation device on the varistor. In case of insufficient protection, the colour in the display window changes from green to red. The functional state is also displayed by a voltage-free signalling contact (changeover). Rated voltage: 400 V AC lightning test current (10/350 µs): 25 kA protection level with lightning test current < 1.9 kV 25 kA short-circuit withstand rating with max. back-up fuse of 250 A gl telecommunication output: contact: 250 V/0.5 A 48 VDC/0.1 A, type: Weidmüller VPU I 3+1 R 400 V/25 kA, Order No. 1351880000 or equivalent
Short specification Class I arrester for LPL 1 with 25 kA, suitable for 400/690 V TN-CS, TT mains systems. Protection level < 1.9 kV. With remote alert, type: Weidmüller VPU I 3+1 R 400 V/25 kA, order no. 1351880000 or equivalent

Approvals

Approvals CE
ROHS Conform

Related products

Type of connection: Screw connection
Order No.: 1351820000
Type: VPU I 1 400V/25KA
Version:
Surge voltage arrester, Low voltage, without telecomm. contact, Single-phase
Delivery status:
This article will no longer be available in the future.
 
Type of connection: Screw connection
Order No.: 1351840000
Type: VPU I 1+1 400V/25KA
Version:
Surge voltage arrester, Low voltage, without telecomm. contact, Single-phase, TN, IT with N, IT without N, TT
Delivery status:
This article will no longer be available in the future.
 
Type of connection: Screw connection
Order No.: 1351870000
Type: VPU I 3 400V/25KA
Version:
Surge voltage arrester, Low voltage, without telecomm. contact, TN-C
Delivery status:
This article will no longer be available in the future.
 
Type of connection: Screw connection
Order No.: 1351890000
Type: VPU I 3+1 400V/25KA
Version:
Surge voltage arrester, Low voltage, without telecomm. contact, TN-C-S, TN-S, IT with N, IT without N, TT
Delivery status:
This article will no longer be available in the future.
 
Contact
Weidmüller Interface GmbH & Co. KG
 
+49 5231 14-0
+49 5231 14-292083
More information
Decentralised automation solutions
Energy Management Solutions
Industrial Analytics
Industrial IoT Solutions
More information
Mobility Concepts
Photovoltaics
Wind Solutions
Workplace Solutions
More information
Single Pair Ethernet
Weidmüller Configurator
Support & Service
Contact
Disposal Instructions
Engineering data
Repairs and replacement parts