Standard signal passive isolator, input-loop powered 1channel passive isolator in 17.5 mm with, input-loop powered, for transmitting and isolating DC current signals 0/4...20 mA
Add-on housing for TS35 DIN rail installation Dimensions: L/B/H 92.4/ 17.5/ 112.4 mm Screw connection/ Nominal cross-section 2.5 mm2 Protection degree: IP 20
Input 0/4...20 mA Output 0/4...20 mA Voltage drop approx. 3 V at RL 0 Ohm, 13 V at RL = 500 Ohm (20 mA) Load resistance < 500 Ohm Transmission error < 0,1 % v. E. Auxiliary power 0/4...20 mA input current loop Ambient temperature range -25 °C...+70 °C
Isolation EN 50178 , 2-way isolation up to 4 kV AC/DC Test voltage 6 kV Rated voltage 300 V AC/DC at overvoltage category III and pollution degree 2 Approvals cULus, cULusEX, CSA, GL
TypeWAS5 CCC-LP 0-20/0-20mA
Short specification
Standard signal passive isolator, input-loop powered 1-channel signal passive isolator in 17.5 mm width with input current loop feed, for transmitting and isolating analogue DC current signals from 0/4 to 20 mA
Standard signal passive isolator, input-loop powered 1channel passive isolator in 17.5 mm with, input-loop powered, for transmitting and isolating DC current signals 0/4...20 mA
Add-on housing for TS35 DIN rail installation Dimensions: L/B/H 92.4/ 17.5/ 112.4 mm Screw connection/ Nominal cross-section 2.5 mm2 Protection degree: IP 20
Input 0/4...20 mA Output 0/4...20 mA Voltage drop approx. 3 V at RL 0 Ohm, 13 V at RL = 500 Ohm (20 mA) Load resistance < 500 Ohm Transmission error < 0,1 % v. E. Auxiliary power 0/4...20 mA input current loop Ambient temperature range -25 °C...+70 °C
Isolation EN 50178 , 2-way isolation up to 4 kV AC/DC Test voltage 6 kV Rated voltage 300 V AC/DC at overvoltage category III and pollution degree 2 Approvals cULus, cULusEX, CSA, GL
TypeWAS5 CCC-LP 0-20/0-20mA
Short specification
Standard signal passive isolator, input-loop powered 1-channel signal passive isolator in 17.5 mm width with input current loop feed, for transmitting and isolating analogue DC current signals from 0/4 to 20 mA
This function is provided via the external service provider https://supplyframe.com. By clicking on "Continue" you will be redirected to this page. This leads to a data transfer of personal data to non-European countries. Please check the data protection policy of the external website, for which Weidmüller assumes no responsibility and liability.